The Schneider BMXAMI0800 is an eight-channel non-isolated high-level analog input module for the Modicon X80 automation platform. It provides higher channel density for machines and process systems requiring multiple standard current or voltage measurements.
The module supports 0–20 mA, 4–20 mA and positive or negative 10 V input signals. Its non-isolated architecture must be considered when designing field grounding, signal commons and cable shielding.
The BMXAMI0800 is suitable for compatible Modicon M340 and X80-based systems. It should not be treated as electrically identical to the isolated BMXAMI0810.
| Model | BMXAMI0800 |
| Series | Modicon X80 |
| Product Type | Non-Isolated Analog Input Module |
| Number of Inputs | 8 |
| Input Level | High Level |
| Isolation | Non-isolated input architecture |
| Current Input Range | 0–20 mA and 4–20 mA |
| Voltage Input Range | Positive or negative 10 V |
| Platform | Compatible Modicon X80 architecture |
| Engineering Software | EcoStruxure Control Expert |
| Legacy Software | Older projects may use Unity Pro |
| Channel Configuration | Configured in the hardware project |
| Grounding | Review signal commons, shields and field grounding |
| Terminal Block | Confirm terminal block and wiring accessories separately |
| Firmware | Verify revision against CPU and project |
| Supply Status | Regional availability varies; confirm before quotation |
The BMXAMI0800 is suitable for process plants, water systems, production machinery, test equipment and automation panels requiring multiple current or voltage measurements.
It may be connected to compatible pressure, flow, level and other analog transmitters. Because the channels are non-isolated, grounding and signal-common design must be reviewed carefully.
Where field circuits have different ground potentials or greater isolation requirements, the BMXAMI0810 may be more appropriate, subject to complete project verification.
Do not substitute BMXAMI0800 and BMXAMI0810 based only on the eight-channel count. Their isolation architecture differs.
Record the existing slot, configured range for every channel, scaling, filtering, diagnostic settings, wiring and terminal-block model before replacement.
After installation, test each active channel and verify that the raw and scaled values match the connected field instruments.
Related models include BMXAMI0410 with four isolated inputs and BMXAMI0810 with eight isolated inputs.
Temperature modules such as BMXART0414 and BMXART0814 belong to a separate functional category.
Please provide the full module reference, rack and CPU models, slot position, signal ranges, grounding arrangement, terminal-block requirement and firmware information.
Product condition, terminal accessories, firmware compatibility, input testing, regional availability and delivery time must be confirmed before quotation.